Enter transformer voltages such as 138000D - 34500Y / 19919, no-load loss, and one or more load-loss values. Base and enhanced ratings are calculated by current-squared scaling (load loss ∝ MVA²), and expected HV/LV current, CT secondary current, transformer efficiency, and voltage regulation are calculated for each MVA. The thermal model section derives SEL guide constants including T1THGR, T1THOR, T1RATL, T1OTR, T1EXPN, and T1EXPM for all three cooling stages.
Saved transformer records
MVA1 / MVA2 / MVA3 are rating fields. ONAN and ONAF are cooling-stage names. This section shows current, CT ratios, efficiency, and voltage regulation.
Example: 138000D - 34500/19919. For Wye, enter either line-line or line-neutral and the missing value is calculated using √3. Delta uses line-line voltage.
Configure the de-energized tap changer side, percent per step, tap range, and selected tap. The table calculates effective line-line voltage and transformer ratio for each tap.
| Position | Tap | Percent | Multiplier | HV L-L (V) | LV L-L (V) | Ratio |
|---|
| Stage | MVA | Load Loss (kW) — Optional |
|---|---|---|
| ONAN Base | ||
| ONAN Enhanced | ||
| ONAF Base | ||
| ONAF Enhanced | ||
| ONAF Base | ||
| ONAF Enhanced |
| Stage | Source | Confidence | MVA | Nominal HV Current (A) | Nominal LV Current (A) | Load-Loss Ratio | Total Load Loss (kW) | Incl. No-Load (kW) | Efficiency (%) | Voltage Reg. (%) |
|---|
| MVA Field | Stage | MVA | Nominal HV (A) | Tap HV (A) | HV Δ (A) | Nominal LV (A) | Tap LV (A) | LV Δ (A) |
|---|
| CT | Ratio | Primary Phase A (A) | Secondary Phase A (A) | Secondary Phase B (A) | Secondary Phase C (A) |
|---|
Selected current: — A per phase. CT secondary current = primary phase current × CT secondary rating ÷ CT primary rating.
| MVA Field | Stage | Output (kW) | Total Losses (kW) | Efficiency (%) |
|---|
| MVA Field | Stage | Z (%) | R (%) | X (%) | Voltage Reg. (%) |
|---|
Temperature rise over oil for ONAN, ONAF1, and ONAF2 stages
T1RATL is load loss divided by no-load loss. T1OTR is the oil thermal time constant: thermal capacity × T1THOR ÷ total watt loss.
| Stage | Cooling | C (thermal cap.) | Total Watt Loss (W) | T1THOR | T1THGR | T1RATL | T1OTR (hr) | T1EXPN | T1EXPM |
|---|
Copy/paste-ready relay settings — values update live as inputs change
| SEL Field | Stage | Value | Units | Formula / Meaning | Copy |
|---|
| Setting | Stage | Recommended Value (°C) | IEEE Basis | SEL Field | Copy |
|---|
A one-page review of the selected assumptions, source confidence, warnings, and main outputs.
"If" power triangle from collected data. Pick a transformer rating, enter the MW you want to study, and adjust power factor. The triangle shows how apparent power and kVAR grow even when real MW looks reasonable.
| Rating | Source | Confidence | Engineer Note |
|---|
Calculates hotspot temperature, aging acceleration factor (FAA), and percent loss of insulation life per IEEE C57.91. Normal insulation life = 180,000 hr.
Compare the current transformer (A) against a second transformer (B) entered manually. Transformer A values are pulled from the current calculator inputs.
| Parameter | Transformer A (Current) | Transformer B (Manual) | Difference (B − A) |
|---|